Features
Low OPEX: | Best in class fuel efficiency with O2E technology |
Robust and Reliable Product: | Lowest maintenance and trouble free product with Kirloskar Liquid Cooled Engines |
Start Type: | Controller Based Easy Push Start Type |
Customer Service: | Quick and affordable door step service coverage (420+ service touch points and 6000+ KOEL trained service professionals on field) |
Warranty: | 2 years warranty & labour free onsite service under warranty period |
KRM: | Critical genset parameters can be views on laptop or mobile |
Prime Rating at rated rpm (as per ISO 8528) |
kVA |
180 |
200 |
250 |
|
kW |
144 |
160 |
200 |
||
Genset Model |
KG1-180WS |
KG1-200ws |
KG1-250WS |
||
Frequency |
Hz |
50 |
50 |
50 |
|
Power Factor |
lagging |
0.8 |
0.8 |
0.8 |
|
Voltage |
V |
415 (3Ø) |
415 (3Ø) |
415 (3Ø) |
|
Governing class (As per ISO 8528 Part – V) |
G3 |
g3 |
G3 |
||
Noise Level |
dBA |
<75 |
<75 |
<75 |
|
Fuel Consumption* |
At 100% Load |
Ltrs/Hr |
41.3 |
45.9 |
56.9 |
At 75% Load |
30.9 |
34.4 |
42.6 |
||
At 50% Load |
22.7 |
25.2 |
29.9 |
||
Fuel Tank Capacity |
Ltrs |
460 |
460 |
460 |
|
Weight of Genset with canopy° |
Dry |
Kg |
3900 |
3900 |
4010 |
Wet |
4300 |
4300 |
4320 |
||
Overall Dimensions of Genset^ |
Length |
mm |
4300 |
4340 |
4340 |
Width |
1740 |
1740 |
1740 |
||
Height |
1970 |
1970 |
1975 |
||
Electrical Battery Starting Voltage |
Volts-DC |
24 |
24 |
24 |
|
Engine |
|||||
Engine Model |
6SL1500TA G2 |
6SL1500TA G2 |
6SL1500TA G3 |
||
Rated output (Prime Continous rating as per ISO 8528-1 |
kW |
183 |
183 |
228 |
|
HP |
248 |
248 |
310 |
||
No. of Cylinder |
Number |
6 |
6 |
6 |
|
Cubic Capacity2 |
Ltrs |
8.86 |
8.86 |
8.86 |
|
Bose x Stroke |
mm |
118 x 135 |
118 X 135 |
118 X 135 |
|
Rated Speed |
RPM |
1500 |
1500 |
1500 |
|
Aspiration |
NA/TC/TA |
TA |
TA |
TA |
|
Lube Oil Change Period |
hrs |
500 |
500 |
500 |
|
Lube Oil Sump Capacity |
Ltrs |
27 |
27 |
27 |
|
Cooling Mechanism |
Liquid Cooled |
Liquid Cooled |
Liquid Cooled |
||
Coolant Capacity |
Ltrs |
32 |
29.2 |
31.8 |
|
Alternator |
|||||
Insulation Class |
Class H |
Class H |
Class H |
||
Ingression Protection |
IP 23 |
IP 23 |
IP 23 |
||
Alternator Efficiency (at 100% load) 0.8pf** |
% |
93 |
93.5 |
93.6 |
|
Max Voltage Dip at Full Load 0.8 pf Lag |
sec |
<20% |
<20% |
<20% |
|
Max Time to build up rated voltage at ated RPM |
< 1 sec provided engine reach the rated speed |
< 1 sec provided engine reach the rated speed |
< 1 sec provided engine reach the rated speed |
||
Short Circuit Ratio |
0.53 |
0.545 |
0.45 |
||
Short Circuit Withstand Time |
sec |
3 time the rated current for < 3 sec |
|||
Overload Withstand Cpacity |
% |
10% overload for 1hr once in 12hrs |
10% overload for 1hr once in 12hrs |
10% overload for 1hr once in 12hrs |
Notes:
- ^ Tolerance Apply, *with 0.845 Specific Graity of Diesel (5% Tolerance)
- ** Efficiency of Alternator as per standards IS 4722 and IEC 34-1
- °These weight are for handling & transportation only
- For Site Conditions other standard operating conditions consult available Prime Power
Disclaimer:
Due to continuous improvement in product on the basis of market feedback above specification are subject to change with out any prior notice. Please contact authorized dealer/distributor for latest specification.